Please Install Flash Player
Download from here
Combustible Gas Detectors (XP-3110)
|
|
Features- For measurement of combustible gas concentration of 0-10/0-100%LEL.
- Suitable for monitoring a risk of explosion.
- New digital display with a simulated analog scale.
- Built-in correction factors for up to 5 flammable gases.(factory option)
|
Specifications
| Model | XP - 3110 | | Gas Detected | Combustible gases and vapors (specify gas to be detected) | | Detection Principle | Catalytic combustion | | Sempling Method | Extractive | | Detection Range | 0 - 100 %LEL | Indication Accuracy (Under identical Conditions) | +5% of full scale | | Alarm Set Value | 20%LEL | | Display | LCD digital (with backlight) Digital display: 0-100%LEL Digital bar display:Auto range changeover 0-10%LEL (L range) 0-100%LEL (H range) | | Alarm Indication | Gas alarm : Intermittent buzzer, red lamp flashing Trouble alarm :L Buzzer, Red lamp flashing, LCD display | | Explosion - Proof Structure | Exib II BT3 | | Operating Temperature | -20 to 50oC | | Power Source | 4 x AA alkaline dry cells | | Battery Life *1 | Up to 20 hours | | Dimensions | W82 x H162 x D36mm | | Weight | Approx. 450 g (160z.) (excluding batteries) | | Standard Accessories | Soft case, 4 x AA alkaline dry cells, Gas sampling hose (1 m), Probe with filter/ moisture trap, spare filters | | Optional Accessories | 2-30 gas sampling hose, Gas dilution probe, Data download software (CD- ROM software and USB cable) |
- Battery life may vary with ambient conditions, conditions of use, storage period,battery manufactures, etc.
|
| |
|
|